Reference: K.A. Snyder, C. Ferraris, N.S. Martys and E.J. Garboczi, Journal of Research of the National Institute of Standards and
Technology, Volume 105, Number 4, July-August, 2000.
PDF Version of Original Paper
Go back to Part I Chapter 7 Sec. (10a) Go back to Table of Contents
Next: Introduction
Using impedance spectroscopy to assess the viability of the rapid chloride
test for determining concrete conductivity
K.A. Snyder, C. Ferraris, N.S. Martys, E.J. Garboczi
Building Materials Division
Building and Fire Research Laboratory
National Institute of Standards and Technology
Abstract:
The suitability of using the initial current from the rapid chloride
test (ASTM C 1202) to determine specimen conductivity is tested
using impedance spectroscopy with a frequency spectrum of 10 Hz to 1 MHz.
The specimen conductivity has an analytical relationship to specimen
diffusivity and so is a useful quantity in service life prediction.
Measurements made on specimens of different lengths indicate
that the total charge passed during the six hour conduction test carried
out according to ASTM C 1202 is not a direct measure of specimen conductivity.
Further, ohmic heating during the six hour test makes it nearly impossible to
directly measure any specimen transport property from the results.
The total charge passed during the six hour conduction test
is, therefore, not a reliable quantity for service life prediction.
Results indicate that the direct current (DC) measurement of resistance using a
potential of 60 volts is sufficient to overwhelm polarization effects,
thereby yielding an accurate estimate of the true specimen conductivity.
Impedance spectroscopy measurements also indicate that corrosion may form on
the brass electrodes, adding bias to a conductivity estimate based
upon a DC measurement.